asked 198k views
5 votes
The nameplate on a 50-MVA, 60-Hz single-phase transformer indicates that it has a voltage rating of 5-kV:74-kV. An open-circuit test is conducted from the low-voltage side, and the corresponding instrument readings are 5 kV, 68.2 A, and 238 kW. Similarly, a short-circuit test from the low-voltage side gives readings of 773 V, 10 kA, and 125 kW. Calculate the equivalent series reactance of the transformer as referred to the high-voltage terminals. Write X in mΩ, If the impedance notation is Z = R + jX.

asked
User Thony
by
7.5k points

1 Answer

3 votes

The equivalent series reactance (X) of the transformer at the high-voltage terminals is roughly 169.2 mΩ.

To calculate the equivalent series reactance (X) of the transformer referred to the high-voltage terminals, we can use the information from the open-circuit and short-circuit tests. The equivalent series reactance X is related to the short-circuit test results.

First, let's calculate the equivalent impedance referred to the low-voltage side
(Z_l) from the short-circuit test:


Z_l = V_{sc / I_{sc

Where:


V_{sc is the short-circuit voltage (773 V)


I_{sc is the short-circuit current (10 kA or 10,000 A)


Z_l = 773 V / 10,000 A = 0.0773 ohms

Now, we need to find the equivalent impedance referred to the high-voltage side
(Z_h). The transformer ratio (a) is given by the high-voltage rating divided by the low-voltage rating:

a =
V_h / V_l = 74 kV / 5 kV = 14.8

The impedance transformation formula for a transformer is:


Z_(h) = a^2 ×
Z_l


Z_(h) = (14.8)^2 × 0.0773 ohms = 169.1824 ohms

Now, you mentioned that the impedance notation is Z = R + jX. To find the equivalent series reactance
X_(h) referred to the high-voltage side in mΩ (milliohms), we need to convert the impedance from ohms to milliohms:


X_(h) = 169.1824 ohms × 1000 mΩ/ohm = 169,182.4 mΩ

So, the equivalent series reactance (X) of the transformer referred to the high-voltage terminals is approximately 169,182.4 mΩ.

answered
User Dave Novo
by
9.0k points