The equivalent series reactance (X) of the transformer at the high-voltage terminals is roughly 169.2 mΩ.
To calculate the equivalent series reactance (X) of the transformer referred to the high-voltage terminals, we can use the information from the open-circuit and short-circuit tests. The equivalent series reactance X is related to the short-circuit test results.
First, let's calculate the equivalent impedance referred to the low-voltage side
from the short-circuit test:

Where:
is the short-circuit voltage (773 V)
is the short-circuit current (10 kA or 10,000 A)
= 773 V / 10,000 A = 0.0773 ohms
Now, we need to find the equivalent impedance referred to the high-voltage side
. The transformer ratio (a) is given by the high-voltage rating divided by the low-voltage rating:
a =
= 74 kV / 5 kV = 14.8
The impedance transformation formula for a transformer is:
= a^2 ×

= (14.8)^2 × 0.0773 ohms = 169.1824 ohms
Now, you mentioned that the impedance notation is Z = R + jX. To find the equivalent series reactance
referred to the high-voltage side in mΩ (milliohms), we need to convert the impedance from ohms to milliohms:
= 169.1824 ohms × 1000 mΩ/ohm = 169,182.4 mΩ
So, the equivalent series reactance (X) of the transformer referred to the high-voltage terminals is approximately 169,182.4 mΩ.