Step-by-step explanation:
The given data is as follows.
 Initial temperature of the system (
 ) =
) = 

So, at state 1 quality of the system is (
 ) = 0.5036
) = 0.5036 
 Pressure at state 2, (
 ) = 6 bar
) = 6 bar
As, it is a rigid tank hence, the specific volumes at state 1 and state 2 are equal.
So, 

Now, from the saturated refrigerant-22 table taking specific volume at 
 is as follows.
 is as follows.
 

 

Thus, 

 = 

 = 0.0007427 + 0.5036 (0.0926 - 0.0007427)
 = 

Hence, 
 =
 = 

Super heated refrigerant-22 tables take pressure at 6 bar. Interpolation method used to find the temperature is as follows.
 
 and
 and 
 
 
 
 and
 and 

 

 = 

 = 40 + 3.75
 = 

Saturated vapor refrigerant-22 takes specific volume at 
 .
.
Therefore, interpolation method used to find the temperature will be as follows.
 
 and
 and 

 
 and
 and 
 
 
 

 = 

 = -1.45 + 1.50
 = 

Thus, we can conclude that at 
 tank contains only saturated vapor.
 tank contains only saturated vapor.